Security Link SL150 Instrukcja Naprawy Strona 42

  • Pobierz
  • Dodaj do moich podręczników
  • Drukuj
Przeglądanie stron 41
SL150 Installation and Setup Guide
6–6
5800 Series Transmitters Table
Also refer to
Appendix A
for transmitter input loops/button locations.
Model Description Input Type and Special Notes
5801 Wireless Panic
Transmitter
Enroll as “3” for RF (supervised), or “4” for UR (unsupervised).
Unit has 4 pushbuttons, each with a unique input (loop) code.
Each pushbutton must be assigned to a zone.
Note:
Input loop (button) No. 4 must always be used.
5802
5802CP
Pendant Belt Clip
(Personal Emergency)
Transmitters
Enroll as “5” for BR (button-type transmitter).
5802MN Miniature Personal
Emergency Trans.
Enroll as “3” for RF (supervised), or “4” for UR (unsupervised).
Single pushbutton-type transmitter.
5804
5804BD
Wireless Key
Transmitter
Enroll as “5” for BR (button-type transmitter).
Has 4 pushbuttons, each with a unique input (loop) code.
Each pushbutton must be assigned to a zone.
Note:
All buttons must be assigned the same input type.
5806
5807
5808
Wireless Photoelectric
Smoke Detectors
Enroll as “3” for RF (supervised).
At the “INPUT S/N” prompt, fault the detector as follows:
1.
On many detectors, you must press a special test switch (not test button) to
fault the detector (see detector’s instructions).
Note:
With some detectors, you must short two contacts to fault the detector.
Disengage the detector’s cover and swing it open. These contacts are on the
PC board near a blue jumper (see detector’s instructions). Momentarily short
these contacts with a small screwdriver.
Two keypad beeps will occur when the detector is faulted the first time.
2.
Wait 6 to 8 seconds, then press and release the test switch (or momentarily
short the contacts) again. 3 beeps will sound if the control has accepted the
input code, and the enrolled input (loop) number will be displayed.
5816
5816MN
Door/Window
Transmitter
Enroll as “3” for RF (supervised).
Has two unique input (loop) zones: one for a wired closed-circuit contact loop,
and the other for a built-in reed switch (used in conjunction with a magnet).
Either or both may be used.
5817 Multi-Point Universal
Transmitter
Enroll as “3” for RF (supervised).
Has three unique input (loop) codes: one for a DIP switch-set “Primary” contact
loop, and the others for two “Auxiliary” closed-circuit contact loops.
The “Primary” loop may be set for:
Repeating or Single Transmission
Normally Open or Normally Closed-circuit
Slow or Fast Response
3-Minute or No Transmission Inhibit
DIP Switches:
Set all DIP switches to the OFF position when enrolling the serial
number.
Note:
All loops must be assigned the same input type.
5818 Recessed Magnetic
Contact Transmitter
Enroll as “3” for RF (supervised).
5819 Shock Processor
Transmitter
Enroll as “3” for RF (supervised).
Has three unique input (loop) zones: one for a wired closed-circuit contact loop,
one for use with inertia-type shock detectors (mounted externally), and one for a
built-in reed switch (used in conjunction with a magnet).
5849
5850
Glassbreak
Detector/Transmitter
Enroll as “3” for RF (supervised).
5890 PIR Detector/
Transmitter
Enroll as “3” for RF (supervised).
The cover must be on the unit when enrolling the serial number.
When “enrolling” a transmitter’s ID code(s), any PIR in the vicinity that is not being enrolled should be covered with a
cloth, tissue, etc. to prevent activation.
Przeglądanie stron 41
1 2 ... 37 38 39 40 41 42 43 44 45 46 47 ... 143 144

Komentarze do niniejszej Instrukcji

Brak uwag